After review by the development team, it has been determined that this behavior is as designed. See the Additional Information section for details.
|
Additional Information
The Connection Point::Overhead Solid Connection placed midspan along the Medium Voltage Conductor does not have Lifecycle Status configured as 'In Service' which makes this a condition barrier as defined in the subnetwork definition for the tier. Updating the Lifecycle Status enables the subnetwork trace to complete and displays the expected Phases Energized on downstream features after running the Update Subnetwork.
Workaround
Configure the Lifecycle Status of the newly placed Connection Point so that it is not a barrier for the subnetwork trace.